Apollo Protocols 16 zones Single Loop Analogue Addressable Control Panel
SmartX 116 AP is a single loop Analogue Addressable Fire panel based on Apollo’s S90, XP95 and Discovery protocols.
SmartX 116 AP is a single loop Analogue Addressable Fire panel based on Apollo’s S90, XP95 and Discovery protocols.
The SmartX fire panel has the following characteristics:
Number of loops | 1 |
Loop current | 400mA |
Protocols | S90, XP95 & Discovery |
Fire Zones | 16 |
Zonal indicators | 16 |
Mains Power | 220 VAC 50Hz |
Conventional zones | 2 (Maximum 20 detectors per zone) |
Conventional zones termination resistors | 4,7KOhms / 1W |
Mains supply fuse | 1,6A 250V |
Power Supply | 24 VDC / 2,5A |
AUX output | 24 VDC ±10% , 700mA max, current limited, monitored |
Battery Backup Power | 2x 12V / 7Ah sealed lead acid gel batteries |
Battery health monitoring (periodic load test) | Every 90 seconds |
Supervised siren outputs | 2 outputs, 24VDC ±10%, 1A max, fused and monitored |
Generic trouble output (on main unit) non monitored | Dry relay contacts NO – C – NC |
Analogue Inputs | 2 intern AUX pulled up inputs 1.5mA sinc current |
Relay Outputs | 2 general relay outputs N/O or N/C (jumper selectable) dry contacts 28V/3A max |
PGM Outputs | 4 PGM outputs Open collector, 200mA sink max current, 30V max handling |
Earth faults detection and indication | Front panel LCD indication & buzzer |
Display | 4 lines of 20 characters LCD |
Enclosure | Epoxy powder coated metal box |
IP rating | IP30 |
Construction | 1.2mm steel sheet powder coated in grey color |
Environmental | Class A temperature range: -5 to 40 °C (23 to 104 °F) Humidity: 5 to 95% RH, non condensing |
Terminal blocks rating | All terminals rated for 12 to18 AWG (0.75 to 2.5 sq mm) |
Dimensions (HxWxD [mm]) | 315 x 425 x 100 |