- FRTCP-IP module connects directly with Fighter panel’s main board (LAN-RS232 connector).
- FRTCP-IP gives the ability to access and control the Fighter fire alarm panel, locally through the RS232 port or remotely through the ethernet / internet (TCP/IP) in real time with the use of the specially designed SmartView software.
- Programming of the FRTCP-IP module’s communication parameters is performed through the Fighter panel’s keypad.
| Power supply | |
| 10 pin box connector | 5VDC or 12-24 VDC |
| 2 way terminal block | 12-24VDC |
| Consumption | 250mA MAX |
| Connections | Ethernet, Serial RS232 |
| RS232 | |
| Ground Isolation | 50 V |
| Connector | Female D9 |
| Ethernet | |
| Ground isolation | Complete galvanic isolation |
| Connector | RJ45 |
| Ethernet type | 10/100 Mbps |
| Indications | |
| Power | Lit when the device is powered |
| Fault | Indicated that isolation voltage is more than 50 V |
| LED1 | Remote client is connected. |
| Others | |
| Dimensions | 10.5 x 7.5 cm |
| Ambient conditions | 0-50°C, 95% max RH |